The value of the output current is regulated by mounting a resistor with the appropriate resistance (according to the datasheet).

Electrical data
Rated input voltage: 220 ... 240 V
Line frequency: 0/50/60 Hz Hz
Input voltage, alternating current: 198 ... 264 V
Input voltage, direct current: 176 ... 276 V
Current set: LEDset
Total harmonic distortion: <10%
Power factor: λ> 0.95
Efficacy of EUZ: 92%
Power losses: 3.0 W
Protective conductor: <0.5 mA
Initial inrush current: 30 A
Max. SE with fuse 10 A 19
Maximum number of SE per 16 A switch 30
Resistance to nap. Impact: (L / N-earth) 2 kV
Impact resistance: (L-N) 1 kV
Rated output voltage: 54 ... 216 V
U-OUT (operating voltage): <250 V
Rated output current: 65 ... 350 mA
Output current tolerance: ± 3%
A frequency of the output current: (100 Hz) <1%
Rated power: 4.1 ... 35 W
Galvanic isolation: Non-isolated
Isolation between the first and the second circuit -

Dimensions and weight
Length: 280.0 mm
Width: 30.0 mm
Height: 21.0 mm
A distance of mounting holes, length: 270.0 mm
Product weight: 185.00 g
Wire cross-section, input side: 0.5 ... 1.5 mm²
Wire cross-section, output side: 0.5 ... 1.5 mm²
Cable length, input side: 8.5 ... 9.5 mm
Cable length, output side: 8.5 ... 9.5 mm

Temperatures and working conditions
Ambient temperature range: -25 ... + 60 ° C
Maximum temperature at the measuring point tc: 75 ° C
Max. Housing temperature: 110 ° C
Relative humidity: 5 ... 85%

Durability
Durability: SE 50000 h

Additional product data
Housing (with admixtures): No.
Opportunities. Dimming.: No.
Overheat protection.: Automatically reversible
Overload protection.: Automatically reversible
Short-circuit protection: Yes
Without protection anti-overload: Yes
Max. Length of wires for a 2.0 m lamp/module LED
Suitable for luminaires with protection class: I
Suitable for emergency lighting: Yes
Connection type, on the output side.: Clamp

Certificates and Standards
Marks of CE testing stations
Signs of the EL research station
Marks of VDE-EMC research stations
The characters of the ENEC 10 research station
Characters of CCC research stations
Characters of RCM research stations
Standards By EN 61347-1 / Wg. EN 61347-2-13 / Wg. EN 55015 / Wg. EN 61547 / Wg. EN 61000-3-2 / Wg. EN 62384 / Acc. to EN 62386
Protection class I
IP20 protection type

 

Datasheet for download OT FIT 35/220-240/350 D LT2 L